Specification
Isolation Transformer
In-Built
Flexible Battery Option
Yes
Paralleling Kit for Synchronising
Not Available
Technology
Double Conversion Online
Filtering
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449
Output Capacity (KVA )
50 KVA
Output Capacity (KW )
40 KW
Output Power Factor
0.8 Power Factor
Other Output Voltage
380 Or 400 Volt
Efficiency at Full Load
> 92 %
Output Voltage Distortion
< 3 %
Output Frequency (sync to mains)
50/60Hz +/- 3 Hz
Output Frequency (not synced)
+/- 0.1% for 50/60Hz Nominal
Output Voltage THD
< 3% linear load and <5% non-linear load
Output Connections
Hard Wire 5-wire (3PH + N + G)
Bypass
Built-in Static Bypass
Overload Capacity
150% for 1 minute 125% for 10 minutes
Other Input Voltage
385 Or 415 Volt
Input frequency
50 Or 60 Hz
Input frequency Range
45 - 55 Hz
Input Voltage Range for Main Operations
385 - 415 Volt
Input Connections
Hard Wire 5-wire (3PH + N + G)
Battery DC Bus
360 - 480 VDC
Battery Type Compatibility
SMF Battery
Battery Circuit Breaker
Optional
Approved Battery Capacity (AH)
42 - 100 Amp.
Maximum Charger Capacity
10 Amp.
Communication & Management
Control panel
LCD Display
Power Management Software
Not Available
Interface Port(s)
RS-232, USB
Audible Alarm
Audible and visible alarms prioritized by severity
Audible noise at 1 meter from surface of unit
< Decibal
Operating Temperature
0 - 40 °C
Operating Relative Humidity
0 - 95 %
Storage Temperature
-20 - 50 °C
Storage Relative Humidity
0 - 95 %
Storage Elevation
0 - 15000 Meters
Other Environmental Compliance
Compliant